Inputs/outputs, Configuration parameter, Parameters – West Control Solutions KS98-1 User Manual

Page 147

Advertising
background image

Alarm with offset (

x1 - x0):

x1 can be shifted by means of x0. This corresponds to the offset of the adjusted alarm limits (L1, L2, H1 and H2) in par -
allel to the x-axis.

Inputs/outputs

Analog input
x1

Input value to be monitored

Digital outputs
L1

Low alarm 1 - becomes logic 1, if

x1 < L1

L2

Low alarm 2 - becomes logic 1, if

x1 < L2

H1

High alarm 1 - becomes logic 1, if

x1 <H1

H2

High alarm 2 - becomes logic 1, if

x1 <H2

Analog output
y1

Calculated and limited input signal

x1

.

Configuration parameter:

Parameter

Description

Range

Default

Select

Selection of the variable to be monitored

x1

x1

t

D alarm

dx1/dt

Alarm with offset

x1-x0

Parameters:

Parameter

Description

Range

Default

H1

High alarm 1

-29 999 ... 999 999

9999

H2

High alarm 2

-29 999 ... 999 999

9999

L1

Low alarm 1

-29 999 ... 999 999

-9999

L2

Low alarm 2

-29 999 ... 999 999

-9999

x0

Offset x0

-29 999 ... 999 999

0

Xsd

Switching hysteresis

0 ... 999 999

1

Limit value signalling and limiting

9499-040-82711

III-147

ALLP ( alarm and limiting with fixed limits(No. 40))

Xsd

min

max

L1, L2

H1, H2

x

Fig. 10 Switching hysteresis and alarm limits:

+x

0

-x

0

x

y

Fig. 11 Offset of the alarm limits