Parameter

Description

Value

Default

x1a in

Measured value correction Inp_a, P1 input value

Real

0

x1aOut

Measured value correction Inp_a, P1 output value

0

x2a in

Measured value correction Inp_a, P2 input value

100

x2aOut

Measured value correction Inp_a, P2 output value

100

x1b in

Measured value correction Inp_b, P1 input value

0

x1bOut

Measured value correction Inp_b, P1 output value

0

x2b in

Measured value correction Inp_b, P2 input value

100

x2bOut

Measured value correction Inp_b, P2 output value

100

Configuration

Description

Value

Default

Typ_a

Voltage 0...10V

0

0

Voltage -50...1500mV

1

Fail_a

Switched off

0

1

Upscale, Inp_a = x100_a

1

Downscale, Inp_a = x0_a

2

Substitute value, Inp_a = XaFail

3

Xakorr

Measured value correction Inp_a switched off

0

0

Measured value correction Inp_a effective

1

Typ_b

Voltage 0...10V

0

0

Voltage -50...1500mV

1

Fail_b

Switched off

0

1

Upscale, Inp_b = x100_b

1

Downscale, Inp_b= x0_b

2

Substitute value, Inp_b = XbFail

3

Xbkorr

Measured value correction Inp_b switched off

0

0

Measured value correction Inp_b effective

1

a0_a

Physical value Inp_a at 0%

Real

0

x100_a

Physical value Inp_a at 100%

Real

100

XaFail

Substitute value with sensor error at Inp_a

Real

0

Tfm_a

Filter time constant of Inp_a in seconds

Real

0,5

x0_b

Physical value Inp_b at 0%

Real

0

x100_b

Physical value Inp_b at 100%

Real

100

XbFail

Substitute value with sensor error at Inp_b

Real

0

Tfm_b

Filter time constant of Inp_b in seconds

Real

0,5

9499-040-82711

Modular I/O - extension-modules

U_INP (analog input card -50...1500mV, 0...10V)

III-306