The self-tuning statuses are indicated with priority in
the display field for manual operation.

w

Self-tuning running, display:

ORun

w

Self-tuning faulty, display:

OErr

Self-tuning completed with an error is finished by
pressing key H twice.

Self-tuning cancelation

Self-tuning can be stopped at any time by pressing key
H, or by selecting Stop in the Stat field (status).

Operating pages

9499-040-82711

I-44

Controller

t

W

X

Y

Cancellation

t

W

X

Y

Cancellation

>1 Std.

t

W

X

Y

Cancellation

t

W
X

Y

Cancellation

t

Ymax

Y

Cancellation

{Y<5%

t

W

X

Y

Cancellation

<10% W0..W100

>1 Std.

Fig.30: Controller page with started self tuning

ORes1/2

Signification or trouble cause

Possible solution

0

No attempt was made or attempt cancelled by

Stat: Stop or

switchover to manual mode ( H key) .

1

Cancellation:
Faulty correcting variable output action,
X does not change in the direction of W.

Change controller
output action.

2

Finished: self-tuning was completed successfully (reversal point found, safe estimation)

3

Cancellation:
The process does not respond or responds too
slowly (change of {X smaller than 1% in 1 hour)

Close control loop.

4

Completed, withou6

AdaErr:

Successful attempt, process has a low reversal point

Optimum result with low re-
versal point

Cancellation, with

AdaErr:

Attempt failed, process stimulation low
(Reversal point found, but estimatio n is unsafe

Increase output step change
dYopt.

5

Cancellation:
Self-tuning cancelled because of exceeded

hazard.

Increase separation of pro-
cess value (X) and (W) when
starting, or decrease

YOptm .

6

Completed: attempt successful, but self-tuning cancelled due to exceeded hazard.

(Reversal point not reached so far; safe estimation).

7

Cancellation:
Output step change too small, {Y < 5%.

Increase

Ymax or set

Yoptm to a smaller value.

8

Cancellation:

reserve too small, or exceeded

whilst PiR monitoring is busy.

Vary stable correcting vari-
able

YOptm.

Signification of self-tuning messages