Csend 184, Send module 184 – West Control Solutions KS98-1 User Manual

Page 184

Advertising
background image

Parameter and configuration data

Configuration

Description

Range

Default

NodeId

Node address of the sending KS98-1 (The sending KS98-1 is adjusted accordingly in engineering tool window
"CANparameter ".) r see *1

* 1) The node address of the sending KS98-1 is adjustable in engineering tool window "CANparameter” or via the

instrument parameters on the front panel (during off-line mode).

III-12.2

CSEND (Send mod. blockno.'s 21, 23, 25, 27 - (No. 57))

Function CSEND provides data for other KS98-1 units on the CANopen bus. The data can be read by the other
multifunction units using the CRCVfunction.

Inputs and outputs

Analog inputs

X1...X9

Analog values 1 to 9, which are sent.

Digital inputs

di1...di9 Digital values 1 to 16, which are sent.

Digital output

valid

0 = invalid data (e.g. no KS98-1 but only KS 98-1)

1 = data could be received

Parameter und Konfigurationsdaten

Configuration

Description

Range

Default

delta

Change from which a new send operation is started.

0,000...999 999

0,1

a

Transmission is at intervals of 200ms.
Note that there is a risk of data loss for values which are available only during 100 ms.

KS 98-1- KS 98-1 cross communication (CANopen)

9499-040-82711

III-184

CSEND (Send mod. blockno.'s 21, 23, 25, 27 - (No. 57))

Dev. data

Langu.

21 23 25 27

(

,

,

)