Nt t – West Control Solutions KS98-1 User Manual

Page 127

Advertising
background image

Analog inputs
x1

Input variable to be integrated

Preset

External preset value

Digital outputs
max

= 1 exceeded with max. limiting

min

= 1 exceeded with min. limiting

Analog output
y1

Integrator output after elapse of integration t

n ts

= ×

Parameters:

Parameter

Description

Range

Default

T

Time constant in s

0.1...999 999

60

x0

Constant

-29 999...999 999

0

y0

Preset value

-29999...999 999

0

Min

Min. limiting

-29999...999 999

1

Max

Max. limiting

-29999...999 999

0

Mode

Source of preset = Para y0

0

0

Source of preset = InpPreset

1

Ramp function:

With constant input x1+x0, the applicable formulas are

y t

y t

n

ts

T

x

x

1

0

1

0

( )

( )

(

)

=

+ Ч Ч +

t

n ts

= ×

t is the time required by the integrator for changing output y1 linearly by value x1 + x0 after integration start.

Ramp response:

The function has a ‘memory’. This means: after power-on, it continues operating with values y1, z1 and z2, which ex -
isted at power-on, provided that the RAM data are still available.

Example: Which is the value of output variable y after t=20s with a time constant of 100s, if a constant of x1 = 10 Volt
is preset. Sampling interval ts is 100ms.

n

t

t

s

=

n

s

s

s

=

=

20

01

200

,

y

after

s

= + Ч

Ч =

0 200

01

100

10

2

20

,

_

_

This results in a gradient of 2V/20s or 0.1Volt /1s.

Time functions

9499-040-82711

III-127

INTE (integrator (No. 51))

Fig. 6

Advertising