West Control Solutions KS98-1 User Manual

Page 212

Advertising
background image

As the throughput times with a search run dependent on the number of segments may be very long, searching is limit -
ed to several time slots so that searching is done only in one segment per time slot.

A search run is done in the following cases :

• Search run at program start: search over several segments up to the next gradient change
• search run started via control input, interface or via operation: forward and backward search from the

actual program point to the next gradient change

• Search run after power failure at

PwrUp = 1: forward and backward search from the point of failu-

re to the next gradient change

• Search run after power failure at

PwrUp = 2: forward and backward search from the program time

in which the program would be without power failure until the next gradient change

• Search run in the hold segment (Gradient =0): A search run is done only if there is min. one further seg -

ment (except hold segment) in this section. With a further hold segment directly before or behind this
segment, the search run takes place only in the actual segment.

+

Search run at TPrio = 1 (time priority): The search run is limited to the actual segment, i.e. the runs from the actual pro -
cess value to the segment end value within the actual remaining segment time.

+

Segments with wait status at the end do not limit the search range, exept it 's the search run after voltage failure!

+

A search run may lead to program termination.

Analog programmer operating page

Analog programmer APROG has an operating page, which can be selected in the operating page menu with input

hide‘ not connected.

If the FB inputs (function block inputs) allocated to the input fields in the following table are assigned to the enginee -
ring, operation (change) of this input field is not possible.

Ü

Name of programmer block

*

Recipe name:

Ö

Process value

ä

Segment number

#

Status (r/w) automatic/manual

<

Block change

>
y

Segment start and end value

x

Remaining segment time

c

Program net time

v

Remaining program time

Status (r/w) stop, run reset, search,
program, quit, error

˜

Status (r) halt, end

Programmer

9499-040-82711

III-212

APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))

Ь

*

Ц
д

#

<

>

y

x
c

v

b

n

m

Fig. 44

Advertising