As the throughput times with a search run dependent on the number of segments may be very long, searching is limit -
ed to several time slots so that searching is done only in one segment per time slot.

A search run is done in the following cases :

• Search run at program start: search over several segments up to the next gradient change
• search run started via control input, interface or via operation: forward and backward search from the

actual program point to the next gradient change

• Search run after power failure at

PwrUp = 1: forward and backward search from the point of failu-

re to the next gradient change

• Search run after power failure at

PwrUp = 2: forward and backward search from the program time

in which the program would be without power failure until the next gradient change

• Search run in the hold segment (Gradient =0): A search run is done only if there is min. one further seg -

ment (except hold segment) in this section. With a further hold segment directly before or behind this
segment, the search run takes place only in the actual segment.

+

Search run at TPrio = 1 (time priority): The search run is limited to the actual segment, i.e. the runs from the actual pro -
cess value to the segment end value within the actual remaining segment time.

+

Segments with wait status at the end do not limit the search range, exept it 's the search run after voltage failure!

+

A search run may lead to program termination.

Analog programmer operating page

Analog programmer APROG has an operating page, which can be selected in the operating page menu with input
‘

hide‘ not connected.

If the FB inputs (function block inputs) allocated to the input fields in the following table are assigned to the enginee -
ring, operation (change) of this input field is not possible.

Ü

Name of programmer block

*

Recipe name:

Ö

Process value

ä

Segment number

#

Status (r/w) automatic/manual

<

Block change

>
y

Segment start and end value

x

Remaining segment time

c

Program net time

v

Remaining program time

—

Status (r/w) stop, run reset, search,
program, quit, error

˜

Status (r) halt, end