III-8

Limit value signalling and limiting

III-8.1

ALLP ( alarm and limiting with fixed limits(No. 40))

Signal limiting:

Parameter L1 determines the minimum, H1 the maximum limiting. y1 is limited to the range between L1 and H1. (L1 ß
y1 ß H1). With parameter H1 smaller than L1, a higher priority is allocated with H1. This means that y1 is ß H1.

Limit signaller:

The limit signaller has two 2 low and high alarms (L1, L2, H1 and H2). Configuration parameter

Select can be

used to select the variable to be monitored (

x1, dx1/dt, x1 - x0).

The limit values are freely adjustable as parameters and have an adjustable hysteresis of ? 0.
The smallest separation between a minimum and a maximum limit value is 0.

When an alarm is triggered, the corresponding output (L1, L2, H1 and H2) is logic “1".

D -alarm (

dx1/dt)

Value x1(t-1) measured one sampling interval before is subtracted from instantaneous value x1(t). This difference is di -
vided by calculation cycle time Tr (100, 200, 400, 800ms).

Thus input variable x1 can be monitored for its rate of change.

9499-040-82711

Limit value signalling and limiting

ALLP ( alarm and limiting with fixed limits(No. 40))

III-146

Select

H1

H2
L2

L1

x1

Y1
h1
h2
l1
l2

Xsd

x0

_

H2

L1

H1

Fig. 9 Limiting at H1 < L1