Reserve, Self-tuning start – West Control Solutions KS98-1 User Manual

Page 43

Advertising
background image

reserve:

To permit self-tuning, the distance between setpoint and process value must be higher than 10% of the setpoint range
before self-tuning start.

With inverse controllers, the must be higher than the process value. With direct controllers, it must be smaller.
The determines a limit which is not exceeded during self-tuning.

Self-tuning start

Select function

Stat: OFF/OK and con-

firm it with M.

Stat:OFF/OK blinks and

is switched over to

Stat: Start by pres-

sing I.

Pressing key M starts the self-tuning attempt.
The can be changed also subsequently. After
successful self-tuning, the controller changes to
automatic operation and controls the with the
new parameters.

When ‘Process at rest’ (

PiR) is detected and a

sufficient reserve is provided, the correcting va-
riable is changed by output step (increased with indirect controller, decreased with direct controller).

!

The size of the output step change is set to 100% as standard. In critical processes, this value (parameter dYopt) may
have to be reduced to prevent damage to the process. The parameter is adjustable in the engineering, or via the para -
meter dialogue of the main menu, if the engineering is known . In case of doubt, contact the programming engineer.

When self-tuning is finished with an error (

Ada_Err or 0err on the controller page), the initial correcting varia-

ble is output until self-tuning is finished by pressing key H.

Self-tuning procedure with heating and cooling processes:

(3-point / split-range controller)

Self-tuning starts as with a “heating” process.

After self-tuning end, the controller settings
based on the calculated parameters are made.
This is followed by line-out at the pre-defined ,
until

PiR is reached again.

Subsequently, a step to cooling is made to de-
termine the “cooling” parameters. When can-
celling the cooling attempt, the parameters for
“heating” are also taken over for cooling. No
error message (

Ada_Err) is output.

a

Whilst self-tuning is active, the control function is switched off!

9499-040-82711

Operating pages

Controller

I-43

t

t

Y

100%

0%

X, W

W

X

60s

PiR

Start

H

I

+

+

+

Start

Adaption

Optimisation

finished

> 10% W0/W100

dYopt

Off/Ok

PIR_H

Step

Off/Ok

Fig.: 26 Self-tuning with heating and cooling

t

t

Y

100%

0%

-100%

X

W

60s

60s

PiR

PiR

Start

Adaption

Optimization

heating

ready

Optimization

cooling

ready

Start

+

YOptm

dYopt

Off/Ok

PIR_H

Step

Off/Ok

PIR_K

Step

Fig.29: