Segment types 40, Segment types, Waiting and operator call – West Control Solutions KS98-1 User Manual

Page 40

Advertising
background image

Segment types

Dependent on segment type, the following parameters can be altered:

Wp i Target setpoint
D i

Control value in segment i

Tp i

Segment duration

Rt i

Segment gradient

Typ i Segment type

Ramp segment (time)
With a ramp segment (time), the runs linearly from the start value (end of previous segment) to -
wards the target (Wp) of the relevant segment during time Tp (segment duration).

Ramp segment (gradient)
With a ramp segment (gradient), the runs linearly from the start value (end value of previous seg -
ment) towards the target value (Wp) of the relevant segment. The gradient is determined by para -
meter Rt.

Hold segment
With a hold segment, the end of the previous segment is output constantly during a defined time
which is determined by parameter Tp.

Step segment
With a step segment, the program goes directly to the value specified in parameter Wp.

The reached due to the step change is kept constant during the time determined in parameter Tp.

Waiting and operator call

All segment types can be combined with ”Wait at the end and operator call”.

If a segment with combination ”wait” was configured, the programmer goes to stop mode at the segment end. Now,
the programmer can be restarted by pressing the H-key.

Operating pages

9499-040-82711

I-40

Programmer

Wp

Tp

Wp

Rt

Tp

Wp

Tp

1

2

3

4

Start

Start

H

run

reset

stop

run

End

t

PRESET

control bits 1

control bits 2

START

END

expired program time

program end

H

Fig. 22
1 Segment type = Time
2 Segment type = Hold
3 Segment type = Time and wait
4 Segment type = Gradient

Advertising