Iii-7.3 trst ( hold amplifier (no. 32)) 136, Iii-7.4 selc ( constant selection (no. 33)) 136, Constant selection 136 – West Control Solutions KS98-1 User Manual

Page 136: Hold amplifier 136, Selc 136, Trst 136, Iii-7.3 trst ( hold amplifier (no. 32)), Iii-7.4 selc ( constant selection (no. 33)), Inputs/outputs

Advertising
background image

III-7.3

TRST ( hold amplifier (No. 32))

With control input hold set to 1, instantaneous input value x1 is stored and output at y1. With control input hold set to
0, output y1 follows input value x1.

The function has a ‘memory’. This means: after power-on, it continues operating with the y1 value which existed at
power-off, provided that the RAM data are still unchanged.

No parameters!

Inputs/outputs

Digital input
hold

Storage signal for the

x1

value

Analog input
x1

Process value which can be output stored.

Analog output
y1

Function output

III-7.4

SELC ( Constant selection (No. 33))

Dependent of control signal d1, the four preset parameters of group 1 or of group 2 are output.

Inputs/outputs

Digital input
d1

Selecting the constant group (0 = group 1; 1= group 2)

Analog outputs

d1= 0 = group 1

d1=1 = group 2

y1

c1.1

c2.1

y2

c1.2

c2.2

y3

c1.3

c2.3

y4

c1.4

c2.4

9499-040-82711

Selecting and storage

TRST ( hold amplifier (No. 32))

III-136

x1

y1

hold

y1

y2

y3

y4

d1

C1.1

C1.2

C1.3

C1.4

I

C2.1

C2.2

C2.3

C2.4

II