Inputs/outputs, Configuration parameters, Parameters – West Control Solutions KS98-1 User Manual

Page 149

Advertising
background image

Alarm with offset (

x1 - x0):

x1 can be shifted by means of x0. This corresponds to the offset of alarm limits (L1, L2, H1 and H2) in par-
allel to the x-axis.

Inputs/outputs

Analog inputs
x1

Input value to be monitored

H1

High alarm 1

L1

Low alarm 1

Digital outputs
L1

Low alarm 1 - is logic 1 with

x1 < L1

L2

Low alarm 2 - is logic 1 with

x1 < L2

H1

High alarm 1 - is logic 1 with

x1 < H1

H2

High alarm 2 - is logic 1 with

x1 < H2

Analog output
y1

Calculated and limited input signal

x1.

Configuration parameters:

Parameter

Description

Range

Default

Select

Selection of variable to be

monitored

x1

x1

t

D alarm

dx1/dt

Alarm with offset

x1-x0

Parameters:

Parameter

Description

Range

Default

H2

High alarm 2

-29 999 ... 999 999

9999

L2

Low alarm 2

-29 999 ... 999 999

-9999

x0

Offset x0

-29 999 ... 999 999

0

Xsd

Switching hysteresis

0 ... 999 999

1

Limit value signalling and limiting

9499-040-82711

III-149

ALLV ( alarm and limiting with variable limits (No. 41))

Xsd

min

max

L1, L2

H1, H2

x

Fig. 13 Switching hysteresis and alarm limits:

+x

0

-x

0

x

y

Fig. 14 Offset of the alarm limits