Sequence control 111, Sequencing 111, Step 111 – West Control Solutions KS98-1 User Manual

Page 111: Step function for sequencing 111, Parameters

Advertising
background image

Parameters:

Parameter Description

Range

Default

Mode 1

Source of pulse duration at

z1

Parameter Ti1

Para.Ti1

t

Input Ti1

Input Ti1

Mode 2

Source of pulse duration at

z3

Parameter Ti2

Para.Ti2

t

Input Ti2

Input Ti2

Ti1

Duration of the pulse generated by

d1,when Mode 1 = Para.Ti1 is entered.

0,1...999 999 [s]

1

Ti2

Duration of the pulse generated by

d2, when Mode 2 = Para.Ti2 is entered.

0,1...999 999 [s]

1

III-4.8

STEP (step function for sequencing (No. 68))

The STEP function realizes the individual steps for sequencing.

The function starts with RESET at step 1 and remains at this step, until the relevant condition input d

1

or the skip input

is set from 0 to 1. This is followed by switch-over to step 2. The procedure for all further steps is identical.

The step number is output as a value at output Step.

Example:
Switch-over from step 3 (

Step = 3) to step 4 (Step = 4) is only after the condition at d3 was met (d3 = 1). The con-

dition at

d4 is checked only when calling up the function for the next time. Thus immediate switch-over is prevented. As

long as

d3 = 0, the value of output Step remains 3.

Alternatively, a positive flank at input

skip also leads to switch-over to the next step (independent of the status at

input

d1..d10).

a

The function has a ‘memory’. This means: after power-on, it continues operating with the step at
power-off, provided that the RAM data are still unchanged.

When several switch-over conditions are 1 simultaneously (e.g.

d1, d2, d3, d4 and d5), only the instantaneously

effective input is handled. I.e. in each calculation cycle, switch-over is only by one step. For realizing a sequencing with
more than 10 steps, the STEP function can be cascaded:

The wiring example shows how 2 STEP functions are cascaded. With cascading, step number 1...n is output always as
a value at output

Step of the last follow-up step.

For resetting the cascaded stepping control, reset wiring at the 1st function block is required.

Logic functions

9499-040-82711

III-111

STEP (step function for sequencing (No. 68))

reset
stop
skip

Casc

activ

Step

d1

d10

...

STEP

Reset

Advertising