However, changing to the next programmer block is not complete. Only some of the values and texts (e.g. title) relevant
for the next block are displayed. The remaining elements continue indicating only the master information (see analog
programmer operating page).

In case a change to the operating page menu (page survey) is made in this condition of the operating page, the block
selection remains unchanged. I.e. when calling up the master block again later, the data of the slave block indicated
last are displayed.

Display information which is firmly assigned to the master block:

Recipe name (can be switched over in reset state)
Program net time (adjustable for Preset to time )
Remaining program time
Status display for halt/end
Status display for stop/run/reset/search/program/quit/error (adjustable)

Display information of the actual programmer (master or slave):

Programmer block name
Process value
Segment number (adjustable for preset to segment only with master)
Actual or actual control bits (both adjustable in manual mode)
Segment start and end value
Remaining segment time
Status display for automatic/manual (adjustable, if permitted via manfree input)

As only the master shall decide upon the change of an active recipe, the wiring structure must be of such kind that
changing is effective also for all relevant slave blocks (master ProgNo output

Þ

slave ProgNo input, see above dia-

gram). This kind of master/slave coupling permits only a central recipe change for all blocks coupled accordingly.

Calling up a slave block operating page via the operating page menu (page survey):
When calling up the operating page of a slave programmer via the operating page menu, display of symbol

uu is

suppressed. Easy changing to other blocks connected via the

Bl-no

>

SlavNo coupling as described above is

not possible. Moreover, no data of the connected master are displayed.

To prevent inadmissible adjustments (recipe selection, run/stop/reset) from being offered on a called up operating
page,outputs ProgNo, run and reset of the master programmer should be wired to the relevant slave programmer in -
puts. For plant operation, slave programmer display is suppressed purposefully with

hide

=1 when the page survey

is active (PageNo at status block = 0).

Subordinated parameter page (program editing page):
On the subordinated parameter page, recipe switchover is possible at any time. But switchover acts only on the recipe
parameter display on this page rather than changing to the effective recipe.

Changing directly to the parameters of the next programmer is not possible. For this, the superordinate operating page
of the corresponding programmer must be used.

Programmers without coupling:

On an operating page with a function block which is not connected with other programmer blocks via

Bl-no >

SlavNo coupling, display of symbol uuis suppressed.

9499-040-82711

Programmer

APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))