Iii-20.7 dido (digital input/output card) 309, Dido 309, Digital input/output card (dido) 309 – West Control Solutions KS98-1 User Manual

Page 309: Iii-20.7 dido (digital input/output card)

Advertising
background image

III-20.7

DIDO (digital input/output card)

Digital input/output card, plugs into modular options card C. The DIDO is used for configuration and parameter setting
of digital inputs/outputs

DIDO. Function block calculation is fixed to once per time slot.

Digital inputs:

d1

if configured as an output: hardware output a

d2

if configured as an output: hardware output b

Digital outputs:

slotid

0 = correct module fitted
1 = wrong module fitted

z1

status of hardware input a; if configured as an output: the output value read back

z2

status of hardware input b; if configured as an output: the output value read back

Configuration

Description

Values

Default

Inv_Ia

direct - HW input di1 direct at z1

0

0

inverse - HW input di1inverted at z1

1

Inv_Ib

direct - HW input di2 direct at z2

0

0

inverse - HW input di2 inverted at z2

1

Inv_

direct - d1 direct on HW output do1

0

0

inverse - d1 inverted at HW output do1

1

Inv_Ob

direct - d1 direct on HWoutput do1

0

0

inverse - d2 inverted on HW output do2

1

Mode_a

Input - only HW input d1 at z1

0

0

Output - d1 at HW output do1 with feedback at z1

1

Mode_b

Input - only HW input d2 at z2

0

0

Output - d2 at HW output do2 with feedback at z2

1

Modular I/O - extension-modules

9499-040-82711

III-309

DIDO (digital input/output card)

HARDWARE

SOFTWARE

d1
d2

Mode1

z1
z2

slotid

Inv1

HARDWARE

SOFTWARE