Search run

In the following cases, a search run is carried out:

w

Start via operation

w

Start via interface

w

Start with

search = 1

w

Program start after

Reset

w

After short power failure with

PowerUp = Cont.seg. or Cont.time

Search run in program segment

When starting the search run,

Wp is set to the XVal value, from where it runs towards the segment end value with

actual gradient (

TPrio = Grad.prio) or in the actual segment rest time (TPrio = Time prio).

If the search value is out of the actual segment with

TPrio = Grad.prio, the program is continued at the seg-

ment point next to the search value (actual segment start / end). With segment start value = segment end value (seg -
ment without gradient; holding time), the program is continued at the segment start.

With a step segment (including the APROGD segments with WMode = 1 (step)), the relevant target setpoint is al-
ways used from the segment start.

Search run in program section

Apart from the search run in the actual segment as described above, searching over several segments or search run
switch-off are possible. The various search run functions can be selected via parameter SMode:

• 0 = search run in segment
• 1 = search run in program section
• 2 = no search run

Searching is limited to a section of several segments which have the same polarity sign as their gradient. Hereby, a
hold segment is neutral

Þ no change of polarity sign.

9499-040-82711

Programmer

APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))

III-211

t

x

w

XVal

Wp

Start

search run

Fail

Search run for

TPrio = Zeit Prio

t

x

w

XVal

Wp

Start

search run

Fail

Search run for

TPrio = Grad.Prio