III-2.3

CHAR (function generator (No. 21))

With max. 11 adjustable value pairs, non-linear functions can be simulated or linearized. Each value pair comprises in -
put

x(1) and output y(1). The number of value pairs is determined using configuration parameter Seg (number of seg-

ments +1 corresponds to the number of value pairs).

The value pairs are connected automatically with straight lines so that each input value

x1 provides a defined output

value

y1. If input value x1 is smaller than parameter x(1), the output value is equal to the value of y(1). If input

value

x1 is higher than the highest parameter x(n) the output value is equal to the corresponding y(n) value.

During entry of the configuration parameters, the condition is that the assigned values stand in ascending order
(

x(1) < x(2) <...< x(11)).

Configuration

Description

Range

Default

Seg

Number of segments

1...10

2

x(1)...(11)

Input value for curve point

-29 999...999 999

0...10*

y(1).

..

(11)

Output value for curve point

-29 999...999 999

0...10*

* 0 for

x(1) and y(1), 1 for x(2) and y(2) ... 10 for x(11) and y(11).

Unless one CHAR is sufficient, the following tip might be helpful:

whereby x10 of CHAR I = x1 of CHAR II and x11 of CHAR I = x2 of CHAR II

9499-040-82711

Non-linear functions

CHAR (function generator (No. 21))

III-99

x1

y1

y

x

( 10)

ß

1

2

3

4

5

6 7

8 9 10

y1

y2

y11

x1

x2

x11

...

...

Seg

x11/y11

x1/y1

CHAR II

CHAR I

I

II

CHAR

CHAR

ADSU

x2/y2

CHAR I+II

x10/Y10

Fig. 110