Digital output module 177, Rm_di 177, Rm_do 177 – West Control Solutions KS98-1 User Manual

Page 177: Rm200 digital input module 177

Advertising
background image

III-11.3

RM_DI (RM 200 - (digital input module (No. 15))

Function

RM_DI handles the data from the connected digital input modules.

Inputs and outputs

Analog input

Slotx

Connection of one of the slot outputs of the RM200 node (C_RM2x)

Digital outputs

et-err

0 = no engineering error
detected

1 = engineering error (several RM module functions at a slot)

slotid

0 = correct slot assignment

1 = faulty slot assignment (wrong RM module inserted)

valid

0 = no data

1 = data could be received

di 1

...

di 8

1st to 8th digital input signal

* Slot = conn.-no., socket e.g. 2...10

Parameter and configuration data

Configuration

Description

Value

Default

MTyp

Module type

0: RM241 = 4 x 24 VDC

0

1: RM242 = 8 x 24 VDC
2: RM243 = 4 x 243 VAC

Inv1

Direct or inverse output of input signal 1?

direct

direct

...

...

/

Inv8

Direct or inverse output of input signal 8?

inverse

III-11.4

RM_DO (RM 200 - digital output module (No. 16))

Function

RM_DO handles the data from connected digital output modules.

Input and output modules

Analog input

Slotx

Connection of one of the slot outputs of the RM200 node (C_RM2x)

Digital inputs

do 1...do 8 s for digital inputs 1 to 8