Iii-6 time functions 124, Iii-6.1 lead ( differentiator (no. 50)) 124, Differentiator 124 – West Control Solutions KS98-1 User Manual

Page 124: Lead 124, Time functions 124, Iii-6 time functions, Iii-6.1 lead ( differentiator (no. 50)), Ct t ts = + <1, Ч ч ч +1

Advertising
background image

III-6

Time functions

III-6.1

LEAD ( differentiator (No. 50))

The differentiator forms the difference quotient according to equation:

( )

(

)

( )

(

)

{

}

[

]

y t

T

T

T

y t

t

a

x t

x t

t

y

s

s

s

1

1

1

1

0

=

+

Ч

-

+ Ч

-

-

+

ts

sampling interval

x1(t)

instantaneous x1

T

time constant

x1(t-ts)

previous x1

a

gain

y1(t)

instantaneous y1

y0 output offset

y1(t-ts)

previous y1

C

T

T

Ts

=

+

<1

( differentiation constant )

The complex transfer function reads:

F

a T p

T p

p

( )

= Ч Ч

Ч +1

Inputs/outputs:

Digital input

reset

= 1 causes that y1= y0 and the difference quotient is set to 0.
= 0 starts differentiation automatically.

Analog input
x1

Input variable to be differentiated

Output
y1

Differentiator output

Parameters:

Parameters

Description

Range

Default

a

Gain factor

-29 999...999 999

1

y0

Output offset

-29 999...999 999

0

T

Time constant in s

0...199999

1

Configuration:

Configuration

Description

Value

Default

Mode

Differentiator

operation

Differentiating all changes

0

0

Differentiating only positive changes

dx/dt >0,

1

Differentiating only negative changes

dx/dt <0

2

9499-040-82711

Time functions

LEAD ( differentiator (No. 50))

III-124

a

T

x1

reset

y1

y0

Mode

+

+ -

-

/