External setpoint 261, Gradient control 261, External setpoint wext – West Control Solutions KS98-1 User Manual

Page 261: Gradient control - setpoint changes with gradients, Setpoint functions iii-261, Fig.78, Fig.79

Advertising
background image

External setpoint

Wext

Switching between the internal setpoint (

wi) and the external setpoint (we) is possible only if the parameter

WFuncis adjusted to W/Casc.
The change-over can be triggered via interface or the digital control input

we/wi.

In order to make the internal setpoint effective, on

we/wi must be attached a logic 1. If the external setpoint is to

be active, a logic 0 must be given on

we/wi.

If the digital control input

we/wi is not wired, the external setpoint is effective.

The internal setpoint

W is evaluated with priority. If in a place (interface or the digital control input we/wi) is swit-

ched to internal setpoint it is not possible to switch over to the external setpoint

Wext from another source.

Gradient control - setpoint changes with gradients

Normally, setpoint changes occur stepwisely. Unless this behaviour is required, a gradient can be set-up using parame -
ters

Grw+ and Grw- or Grw2.

If these parameters are set, the setpoint changes are made bumplessly. With digital input ‘

gr_off‘ not set, effec-

tive setpoint

Weff runs linearly towards the changed setpoint (target value), whereby the slope is determined by

gradients

Grw+ and Grw- adjustable at parameter setting level (r see Fig.: 78). For the second W2, an indepen-

dent gradient

Grw2 was introduced, which is valid for both change directions and for w r W2 switchover.

The gradient function is switched off when setting

Grw+ and Grw- or Grw2 to “----”

( engineering tool = off), or with digital input

Gr off set to 1.

Switch-over with gradients (W

rW2, WrWext, controller"on")

The new setpoint is linear started outgoing from the momentary process-value. The slope of the ramp is determined re -
lated to the direction of

Grw+, Grw- and/or Grw2.

+

This principle applies, even if the process-value is outside the adjustable range W0/W100 at switch-over time (e.g.
when starting).

9499-040-82711

Setpoint functions

III-261

Setpoint 1

Setpoint 2

Adjustment of

1

2

Setpoint

Setpoint

r

upper setpoint limit W100

effective setpoint

x

w

Wext

W2

Time

Setpoint, process value

Grw-

Setpoint

Grw+

Adjustment of

Setpoint2

Setpoint 1

r

lower setpoint limit W0

Fig.78:

Setpoint
e.g.

1

W2

Setpoint
e.g.

2

Wext

Setpoint 3
e.g. w

upper setpoint limit W100

effective setpoint

x
w
Wext
W2

Time

Setpoint, process value

Process value

Grw2

Grw-

Grw+

lower setpoint limit W0

Switch over

Setpoint

Setpoint

3

1

r

Switch over

Setpoint

Setpoint

3

2

r

Controller "on"

Fig.79:

Advertising