VALARM (display of all alarms on alarm operating pages (function no. 109)

General

Function block VALARM handles up to 8 alarms. Alarms are displayed and can be acknowledged, if acknowledgement
via parameter setting is required. The alarm conditions are determined by digital inputs a1 ... a8 (0 alarm condition off,
1 alarm condition on).

Inputs/outputs

Digital inputs:
hide

Display of this alarm operating page is suppressed

lock

Operation of this operating page is disabled, i.e. alarm acknowledgement is not possible

a1...a8

Alarm inputs alarms 1 ... 8

Analog output
BL-no

Number of this block

Digital outputs
a1...a8

=1 means that alarm 1 must be acknowledged

Parameter und Konfigurationsdaten

Parameter
a1 ... a8

=1 means that alarm 1 must be acknowledged

Parameter

Description

Values

Default

Typ_a1 ...
Typ_a8

Alarm function

Quit

t

noQuit

9499-040-82711

Additional functions

VALARM (display of all alarms on alarm operating pages (function no. 109)

III-298

VALARM