Iii-7.2 peak ( peak value memory (no. 31)) 135, Peak 135, Peak value memory 135 – West Control Solutions KS98-1 User Manual

Page 135: Inputs/outputs

Advertising
background image

III-7.2

PEAK ( peak value memory (No. 31))

Maximum input value x

max

and minimum input value x

min

are determined, stored and output at

Max and Min. With

the stop input set to 1, the extreme values determined last remain unchanged.

If the

reset input is set to 1, the extreme value memory and any applied stop command are cancelled. (x

max

and x

min

are set to the instantaneous x1 value and follow input x1, until the

reset input returns to 0.)

Unused inputs are interpreted as 0 or logic 0.

The function has a ‘memory’. This means: after power-on, it continues operating with the Min- and Max values which
existed at power-off, provided that the RAM data are still unchanged.

No parameters!

Inputs/outputs

Digital inputs
stop

With the stop input set to 1, instantaneous values Max and Min are unchanged.

reset

The reset input deletes the

Min and Max values.

Analog inputs

x1

Process value, the min and max values of which are output.

Analog outputs
Max

Maximum value

Min

Minimum value

Selecting and storage

9499-040-82711

III-135

PEAK ( peak value memory (No. 31))

Max

Min

x1

xmax

xmin

&

x<y

x>y

stop
reset