I-9.4

Calibration

Press ID to select the input and M to open the calibration page.

Transducer input:
Adjusting the transducer start and end:

Ü

Select

Quit Set transducer to start

*

Press

M r Quit blinks

Ö

Press I r

Set 0% blinks

ä

Wait until the input has settled (min. 6 s)

#

Press M r

0% done is displayed

<

Set transducer to end

>

Press M r

0% done blinks

y

Press I 3x r

Set 100% blinks

x

Wait until the input has settled

c

Press M r

100% done is displayed.

Calibration is finished. For exit from calibration press D until nothing is marked and then press M.

Two resistance thermometers:
Calibration of lead resistance effect

Ü

Select

Quit .

Short-circuit both thermometers in the connecting head

*

Press

M r Quit blinks

Ö

Press I r

Set Dif blinks

ä

Wait until the input has settled (min. 6 s)

#

Press M r

Cal done is displayed

Lead resistance adjustment is finished. Remove both short cir-
cuits. For exit from calibration press D until nothing is marked
and then press M.

I-9.5

Online/Offline

For configuration changing, switch the unit to ‘Offline’ and back to ‘Online’ after alteration.

a

When switching the unit to status off-line, the outputs will remain in the status at switch-over time !!!

+

By switching over to on-line, all data is saved.

+

When terminating the off-line mode by cancellation (Escape config.) the data saved last is loaded back into the wor -
king memory.

9499-040-82711

Instrument settings in the main menu

Calibration

I-35