III-21.2

Sampling intervals

The table opposite shows the sampling intervals for conversion
of the input signals into internal values and conversion of the
internal values into output signals (hardware conversion).
The sampling interval for software calculation of function
blocks AINP1, AINP3...AINP6, DINPUT, STATUS, CONST, LED,
INFO, OUT1...OUT5 and DIGOUT is 100 ms.

Input or output

Sampling interval

INP1

at intervals of 200 ms

INP3 / INP4

at intervals of 100 ms

INP5

at intervals of 800 ms

INP6

at intervals of 400 ms

di1...di12

at intervals of 100 ms

OUT1...OUT5 / do1...do6

at intervals of 100 ms

Calculation of the other function blocks is at equal intervals according to their allocation to the 8 time slots of 100 ms
each. Allocation of a block to one or several time slots (at intervals of 100, 200, 400 or 800 ms) is in the engineering.
For each block, the engineering tool provides an identification (ts) which can be used to determine the allocation from
the table opposite.

The total of calculation times of all required function blocks must be < 100 % for each time slot.

III-21.3

EEPROM data

Data are stored in non-volatile EEPROM. The manufacturers specify approx. 100 000 permissible write cycles per
EEPROM address, in reality, however, this value can mostly be exceeded by a multiple. If parameters and configura -
tions are changed exclusively manually, exceeding the max. number of write cycles is almost precluded. With digital
interface or automatic parameter changes, however, taking the maximum number of write cycles into account is indis -
pensable, and measures against excessively frequent parameter writing must be take

Function management

9499-040-82711

III-311

Sampling intervals

Time slot

ts

1 2 3 4 5 6 7 8 Sampling interval

11

f f f f f f f f at intervals of 100 ms

21

f

f

f

f

at intervals of 200 ms

22

f

f

f

f at intervals of 200 ms

31

f

f

at intervals of 400 ms

32

f

f

at intervals of 400 ms

33

f

f

at intervals of 400 ms

34

f

f at intervals of 400 ms

41

f

at intervals of 800 ms

42

f

at intervals of 800 ms

43

f

at intervals of 800 ms

44

f

at intervals of 800 ms

45

f

at intervals of 800 ms

46

f

at intervals of 800 ms

47

f

at intervals of 800 ms

48

f at intervals of 800 ms