Measured value correction 275, Parameter and configuration data, Measured value conditioning – West Control Solutions KS98-1 User Manual

Page 275

Advertising
background image

Parameter and configuration data

Parameter

Description

Values

Default

x1in

Measured value correction P1, input

-29999 ... 999 999

0

x1out

Measured value correction P1, output

-29999 ... 999 999

0

x2in

Measured value correction P2, input

-29999 ... 999 999

100

x2out

Measured value correction P2, output

-29999 ... 200000

100

Configuration Description

Values

Default

Type

Type L -200...900 °C

Type L

Type J -200...900 °C

Type J

Type K -200...1350 °C

Type K

Type N -200...1300 °C

Type N

Type S -50...1760 °C

Type S

Type R -50...1760 °C

Type R

Type T -200...400 °C

Type T

Type W 0...2300 °C

Type W

Type E -200...900 °C

Type E

Type B 0...1820 °C

Type B

Pt 100 -99,9...850,0 °C

Pt100 850

Pt 100 -99,9...250,0 °C

Pt100 250

2x Pt 100 -99,9...850 °C

2Pt100 85

2x Pt 100 -99,9...250,0 °C

2Pt100 25

0...20 mA

0...20mA

t

4...20 mA

4...20mA

0...10 V

0...10V

2...10 V

2...10V

Transducer 0...500 [

Pot.trans

Resistance 0...500 [ linear

0..500Ohm

Resistance 0...250 [ linear

0..250Ohm

Fail

Fail function off

disabled

Digital output

fail = 1, y1 = x100

Upscale

t

Digital output

fail = 1, y1 = x0

Downscale

Digital output

fail = 1, y1 = XFail

Subst.val.

Xkorr

Measured value correction off

off

t

Measured value correction adjustable

on

Unit

Unit = °C

only effective with

thermocouple and Pt100 setting

°C

t

Unit = °F

°F

STK

Internal temperature compens.

only effective with

thermocouple

int.CJC

t

External temperature compens.

ext.CJC

x0

Physical value at 0%

only effective with standard

signals (0/4..20mA or 0/2..10V)

-29999 ... 999 999

0

x100

Physical value at 100%

-29999 ... 999 999

100

XFail

Substitute value with sensor error

-29999 ... 999 999

0

Tfm

Filtertime constant

[s]

0 ... 999 999

0,5

Tkref

Reference temperature at

STK = ext.TK

0 ... 140

0

Measured value conditioning

Before the pre-filtered (time constant ...; limiting frequency ...) analog
input signals are available as digitized measurement values with
physical quantiy, they are subjected to extensive measured value
conditioning.

Inputs

9499-040-82711

III-275

AINP1 ( analog input 1 (No. 08))

y1

Unit
STK
Tkref

Typ

XFail
Fail

x0

x100

Tfm

x2out

Xkorr

x2in

x1out
x1in