Frame 12 Mechanical Installation

Figure 38 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal
Coat)

Operating Temperatures

Frame 12 drives require a minimum of 5200 m

3

/h (3060 cfm) of cooling air.

200 mm

(8.0 in.) Min.

Powerf

u

l Perform

a

nce, Flexi

b

le Control.

838 mm

(33.0 in.) Min.

Powerf

u

l Perform

a

nce, Flexi

b

le Control.

PowerFlex
Drive

Voltage Class

Amp Rating

Surrounding Air Temperature
Normal Duty

Heavy Duty

700H

400/480V AC
(540/650V DC)

820, 920

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

400/480V AC
(540/650V DC)

1030

0…40

°

C (32…104

°

F)

0…35

°

C (32…95

°

F)

600/690V AC
(810/932V DC)

820, 920

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

600/690V AC
(810/932V DC)

1030

0…35

°

C (32…95

°

F

0…40

°

C (32…104

°

F)

700S

400/480V AC
(540/650V DC)

820, 920

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

400/480V AC
(540/650V DC)

1030

0…40

°

C (32…104

°

F)

0…35

°

C (32…95

°

F

600/690V AC
(810/932V DC)

820, 920

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

600/690V AC
(810/932V DC)

1030

0…35

°

C (32…95

°

F

0…35

°

C (32…95

°

F