Frame 12 Mechanical Installation

Chapter 8

Table 26 - Power Terminal Specifications

Figure 47 - Power Terminal Locations

No. Name

Description

Wire Size Range

(1)(2)

Torque

Terminal Bolt Size

(3)(4)

Maximum

Minimum

Recommended

1

Input Power Terminal Block

(3)

1L1, 1L2, 1L3, 2L1, 2L2, 2L3

Input power

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

2

Output Power Terminal Block

((3)

1U/1T1, 1V/1T2, 1W/1T3,
2U/2T1, 2V/2T2, 2W/2T3

Motor connections

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

3

SHLD Terminal, PE, Motor Ground

(3)

Terminating point for wiring shields

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M10

4

DC Bus

(3)

(2 Terminals; DC–, DC+)

DC input or external brake

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

5

Cable Clamp for Shield

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

Cat No.

1234567890-*

FIELD INSTALLED OPTIONS:

FIELD INSTALLED OPTIONS:

DC- DC+

DC- DC+

1L1

1L2

1L3

2L1

2L2

2L3

1U/T1

1V/T2

1W/T3

2U/T1

2V/T2

2W/T3

Enclosure Style A Shown

1

1

5

5

3

2

2

4

4

Advertising
This manual is related to the following products: