Chapter 4

Communication Options

Figure 13 - PowerFlex 700S Logic Command Word

Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command

Description

x Normal Stop

0 = Not Normal Stop
1 = Normal Stop

x

Start

(1)

(1) A “Not Stop” condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition will start

the drive.

0 = Not Start
1 = Start

x

Jog 1

0 = Not Jog using [Jog Speed 1]
1 = Jog using [Jog Speed 1]

x

Clear Fault

(2)

(2) To perform this command, the value must switch from “0” to “1.”

0 = Not Clear Fault
1 = Clear Fault

x x

Unipolar
Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control

x

Reserved

x

Jog 2

0 = Not Jog using [Jog Speed 2]
1 = Jog using [Jog Speed 2]

x

Current Limit
Stop

0 = Not Current Limit Stop
1 = Current Limit Stop

x

Coast Stop

0 = Not Coast to Stop
1 = Coast to Stop

x

Reserved

x

Reserved

x

Spd Ref Sel0

x

Spd Ref Sel1

x

Spd Ref Sel2

x

Reserved

Bits

14

13

12

0

0

0

= Spd Ref A

0

0

1

= Spd Ref B

0

1

0

= Preset 2

0

1

1

= Ref. 3 (Preset 3)

1

0

0

= Ref. 4 (Preset 4)

1

0

1

= Ref. 5 (Preset 5)

1

1

0

= Ref. 6 (Preset 6)

1

1

1

= Ref. 7 (Preset 7)