Chapter 10

Frame 14 Mechanical Installation

Charging the MCCB Motor Operators

The stored energy motor operators must be charged prior to the first time the
circuit breakers are closed and whenever input power is removed and re-applied
to the drive.

1.

With the doors of the enclosures containing the MCCBs open, apply
control voltage to the drive.

2.

Press and hold the “Open” (red) control button on the enclosure door
until the status text “Charged Spring” displays on each of the MCCBs (see
illustration below).

ATTENTION: When an external device for circuit breaker motor operator status
is not used, the enclosure door(s) must be open in order to view the status
indicator on the circuit breakers. Only qualified personnel familiar with
PowerFlex 700S and 700H drives and associated machinery should plan or
implement the installation, start-up and subsequent maintenance of the
system. Failure to comply may result in personal injury and/or equipment
damage.

CLOSE

OPEN

CLOSE

OPEN

Close and Open buttons location
on enclosure door.