Installation on a grounded b phase delta system – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 146

Advertising
background image

146

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 10

Frame 14 Mechanical Installation

Installation on an Ungrounded Distribution System or High Resistive
Ground

Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page

147

.

Should insulate terminal X4 on the Rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board o
n page

148

.

If you are installing a 600/690V AC input drive on an ungrounded distribution
system or high resistive ground, you:

Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page

147

.

Must insulate terminal X4 on the Rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board o
n page

148

.

Installation on a Grounded B Phase Delta System

If you are installing a drive on a grounded B phase Delta system, you:

Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page

147

.

Must insulate terminal X4 on the Rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board o
n page

148

.