I/o terminal blocks, Wiring the main control board i/o terminals – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 48

Advertising
background image

48

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

I/O Terminal Blocks

Wiring the Main Control Board I/O Terminals

Terminal blocks TB1 and TB2 contain connection points for all inputs, outputs
and standard encoder connections. Both terminal blocks reside on the main
control board in the control cassette. See

Figure 8

below for locations.

Table 17

and

Table 18

on page

49

contain detailed descriptions for the terminals

on TB1 and TB2. Remove the terminal block plug from the socket and make the
appropriate connections. See Removing the Control Cassette on page

55

for

instructions on removing the control cassette from the drive.

Reinstall the plug when wiring is complete. The terminal blocks have keys, which
make it difficult to insert a terminal plug into the wrong socket.

Table 16 - Control & Encoder Terminal Block Specifications

Figure 8 - Main Control Board I/O Terminal Block Locations

IMPORTANT

For NEMA/UL Type 1 applications, all wiring must be routed through the
conduit plate on the drive. Route any wires from the expanded cassette to the
base cassette and out of the drive.

Name

Description

Wires Size Range

(1)

(1) Maximum/minimum sizes the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

I/O Terminal Blocks

Signal & Encoder power
connections

1.5 mm

2

(16 AWG)

0.14 mm

2

(28 AWG)

0.25 N

m

(2.2 lb

in)

0.22 N

m

(1.9 lb

•i

n)

TB1 Terminals

TB2 Terminals

Control