Power wiring, Input power wiring – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 114

Advertising
background image

114

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 8

Frame 12 Mechanical Installation

Power Wiring

Input Power Wiring

Frame 12 drives utilize two parallel power structures, and therefore have two sets
of AC input power terminals. You must supply power to both sets of input
terminals. There are several methods for accomplishing this.

For applications that require that the DC– and DC+ terminals for PowerFlex
700S or 700H frame 12 drives be connected in common (for example, 12 pulse
applications, or when using a dynamic brake), you must purchase and install the
frame 12 DC Bus Connector kit, which is sold separately from the drive. See the
PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit, Installation
Instructions, publication

PFLEX-IN022

.

Figure 43 - Frame 12 AC Wiring Example: Two Fuses per Phase

IMPORTANT

Parallel wiring must have the same cable dimensions, type and routing. Non-
symmetrical wiring may cause unequal loading between the converters and
reduce the drive’s ability to deliver current to the motor.

1L1

1L2

1L3

2L1

2L2

2L3

L1

L2

L3

AC Input Power Terminals Inside Drive

AC Input Power Wiring, Fuses, and Disconnect

Device Provided by Customer

Advertising
This manual is related to the following products: