Chapter 9

Frame 13 Mechanical Installation

Minimum Mounting
Clearances

Operating Temperatures

Frame 13 drives require a minimum of 4200 m3/h (2472 cfm) of cooling air for
the inverter unit and 1150 m

3

/h (677 cfm) of cooling air for each converter unit.

800 mm

(31.50 in.) Min.

200 mm

(8.0 in.) Min.

1600 mm, Style “A” Enclosure Shown.

PowerFlex
Drive

Voltage Class

Amp Rating

Surrounding Air Temperature
Normal Duty

Heavy Duty

700H

All

All

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

700S

400/480V AC
(540/650V DC)

All

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

600/690V AC
(810/932V DC)

920, 1030

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

600/690V AC
(810/932V DC)

1180

0…35

°

C (32…95

°

F)

0…35

°

C (32…95

°

F)