Frame 10 Mechanical Installation
Chapter 6
Disconnect the Small Capacitors from the Input Terminals
Follow the lettered steps below to disconnect the small capacitors from the input
terminals.
IMPORTANT
It is not necessary to remove the power wiring from the terminals in order to
insulate the capacitor leads.
Task
Description
Remove the screws and lock washers that secure each of the three capacitor supply wires to the input power
terminals.
Insulate the capacitor leads and leave disconnected.
Install and tighten the screws and lock washers only.
IMPORTANT
Do not re-install the capacitor leads.
A
B
C
L1
L2
L3
Capacitor
Insulator
Capacitor lead - leave
disconnected
Input power terminal
A
B
C
Front View of Input
Power Terminals
Side View of Input
Power Terminals