Page 46

Advertising
background image

46

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 3

Control Wiring for PowerFlex 700S Drives with Phase II Control

Main Control Board Switch
and Jumper Settings

Table 15 - Switch and Jumper Settings

ATTENTION: The switches for Digital Inputs 4…6 are set to 24V DC at the
factory. If you are running a 115V AC input application, the switches must be set
as indicated below before applying power to the drive or damage to the main
control board may occur.

IMPORTANT

There are two separate values for an encoder

Function

Default

Switch

Open

Closed

Notes

HW Enable Jumper (P22) pins 2-4

HW Enbl

SHUNT
Jumper

pins 2-4
HW Enbl

pins 1-3
No Enbl

No Jmpr = HW Enbl
See Hardware Enable Circuitry on
page

53

for configuration.

Gate Enable Jumper
(P13)

Jumper on
pins 15-16

SHUNT
Jumper

No Jmpr

Jumper on
pins 15-16

No Jmpr = Gate disable or Safe-
Off/Second Encoder board is
present

(1)

(1) Refer to publication

20D-UM007

, DriveGuard® Safe-Off Option for PowerFlex® 700S Phase II AC Drives and PowerFlex 700L Liquid-

Cooled AC Drives, for more information on the Safe-Off Option board, or publication,

20D-IN009

Installation Instructions - Second

Encoder Option Card for PowerFlex® 700S Drives with Phase II Control, for more information on the Second Encoder Option board.

Analog Input 1

Voltage

S5-2

Voltage

Current

Change with Power Off

Analog Input 2

Voltage

S5-1

Voltage

Current

Change with Power Off

Digital Inputs 4-6
Voltage

24V DC

S4-1,
S4-2

115V AC

24V DC

Change with Power Off

Digital Input 1 Voltage

24V DC

S3-1

24V DC

12V DC

Change with Power Off

Digital Input 2 Voltage

24V DC

S3-2

24V DC

12V DC

Change with Power Off

Encoder Supply Voltage

12V DC

S2-4

12V DC

5V DC

Change with Power Off

Typically, set all switches the same

Encoder Signal A Voltage 12V DC

S2-1

12V DC

5V DC

Encoder Signal B Voltage 12V DC

S2-2

12V DC

5V DC

Encoder Signal Z Voltage 12V DC

S2-3

12V DC

5V DC

Function

Switch

Down

Up

Center

Notes

DriveLogix Processor

S1

RUN

PROG

REMOTE

Processor Mode