Frame 14 Mechanical Installation

Chapter 10

Ungrounded, High Resistive
Ground or Grounded B Phase
Delta Installations

Frame 14 size drives are equipped with common mode capacitors. To guard
against drive damage, these capacitors should be disconnected depending upon
the type of ground system on which the drive is installed.

To access and move the common mode jumper(s) and disconnect the capacitor
connections you must first move the control frame and remove the protective
covers from the converter unit. These steps are detailed on the following pages.

Note: See Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives - Installation Instructions, publication

DRIVES-IN001

, for

additional information on an ungrounded distribution system or high resistive
ground installation.

Figure 60 - Common Mode Jumper and Rectifier Circuit Board Location

Converter

Unit

Common

Mode

Jumper

Control Frame not shown for clarity only

Inverter Unit

Inverter Unit

1500A Drives

Drives Above 1500A

Inverter Unit

Converter

Unit

Inverter Unit

Converter
Unit

There is one jumper for
each rectifying module.
The rectifying modules
and jumpers are located
on the left side of the
power stack on the
drive’s converter units.

Rectifier

board

Rectifier

board