Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Removing the 20C-DG1
Option Board

During maintenance or service there may be a need to remove the 20C-DG1
option board.

The drive is designed to generate a non-resettable fault F10 “System Fault” if the
option board is removed. The operator must manually change parameter 358
[20C-DG1 Remove] to 1- “Remove” and then back to 0 - “Ready” to clear and
acknowledge the fault.

Once maintenance or service is completed and the 20C-DG1 option card has
been reinstalled, the drive will recognize the option card on power-up.

Verify Operation

At regular intervals during the life of the machine check the protective system for
proper operation. Both channels shall be verified using the table below. How
frequently the protective system is checked is dependent on the safety analysis of
the machine section controlled by the drive.

Table 25 - Gate Disable Status and Verification

Protective System Status

Drive In

Gate Disable

State

Drive In

Gate Disable

State

Drive In

Gate Disable

State

Drive Able

To Run

Channel Operation

SD1 - terminals X5-1 & X5-2
Par 359 [20C-DG1 Status], bit 3
“No Enable CH1”

Bit 3 = 1

No Power Applied

Bit 3 = 0

Power Applied

Bit 3 = 1

No Power Applied

Bit 3 = 0

Power Applied

SD2 - terminals X5-3 & X5-4
Par 359 [20C-DG1 Status], bit 4
“No Enable CH2”

Bit 4 = 1

No Power Applied

Bit 4 = 1

No Power Applied

Bit 4 = 0

Power Applied

Bit 4 = 0

Power Applied

Description For Verification

PowerFlex 700H Drive Status

Output Disabled Output Disabled Output Disabled

Output Enabled

Par 359 [20C-DG1 Status],
Bit 0 “Gate Disable”
or Bits 2 “Unexp In Pro” and 15
“Unexp HW Pro”

Bit 0 = 1

Bit 2 = 1

Bit 15 = 1

Bit 2 = 1

Bit 15 = 1

Bit 0 = 0

Fault or Alarm

F59 “Gate Disable”

(Fault or Alarm

Based on drive set

up)

F10 “System Fault” F10 “System Fault”

None

Advertising