Chapter 4

Communication Options

Communication
Configurations

Typical Programmable Controller Configurations

Logic Command/Status Words

Figure 11 - PowerFlex 700H Logic Command Word

IMPORTANT

If block transfers are programmed to continuously write information to the
drive, care must be taken to properly format the block transfer. If attribute 10 is
selected for the block transfer, values will be written only to RAM and will not
be saved by the drive. This is the preferred attribute for continuous transfers. If
attribute 9 is selected, each program scan will complete a write to the drives
non-volatile memory (EEprom). Since the EEprom has a fixed number of
allowed writes, continuous block transfers will quickly damage the EEprom. Do
Not assign attribute 9 to continuous block transfers. See the individual
communications adapter User Manual for details.

Logic Bits
15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Command

Description

x

Stop

(1)

0 = Not Stop
1 = Stop

x

Start

(1)(2)

(1) A “0 = Not Stop” condition (logic 0) must first be present before a “1 = Start” condition will start the drive. The Start command acts

as a momentary Start command. A “1” will start the drive, but returning to “0” will not stop the drive.

(2) This Start will not function if a digital input (Pars 361…366) is programmed for “2-Wire Control” (option 7, 8 or 9).

0 = Not Start
1 = Start

x

Jog

0 = Not Jog
1 = Jog

x

Clear Faults

0 = Not Clear Faults
1 = Clear Faults

x

x

Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Present Direction

x

Local Control

0 = No Local Control
1 = Local Control

x

MOP
Increment

0 = Not Increment
1 = Increment

x

x

Accel Rate

00 = No Command
01 = Use Accel Time 1
10 = Use Accel Time 2
11 = Use Present Time

x

x

Decel Rate

00 = No Command
01 = Use Decel Time 1
10 = Use Decel Time 2
11 = Use Present Time

x

x

x

Reference
Select

(3)

(3) This Reference Select will not function if a digital input (Pars. 361…366) is programmed for “Speed Sel 1, 2 or 3” (option 15, 16 or

17). Note that Reference Selection is “Exclusive Ownership.”

000 = No Command
001 = Ref. 1 (Ref A Select)
010 = Ref. 2 (Ref B Select)
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)

x

MOP
Decrement

0 = Not Decrement
1 = Decrement