Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 51

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
51
Control Wiring for PowerFlex 700S Drives with Phase II Control
Chapter 3
Primary Encoder Interface -
Internal Supply
Supports 5V/12V DC
differential encoders with
internal power supply.
Used as primary closed loop
speed feedback.
Using Encoder 0 as speed feedback:
• Par 222 [Motor Fdkbk Sel] = 0 - “Encoder 0” (default)
• Par 232 [Encoder0 PPR] = Pulses/Rev for installed encoder
Primary Encoder Interface -
External Supply
Used as primary closed loop
speed feedback.
Using Encoder 0 as speed feedback:
• Par 222 [Motor Fdkbk Sel] = 0 - “Encoder 0” (default)
• Par 232 [Encoder0 PPR] = Pulses/Rev for installed encoder
Input/Output
Connection Example
Required Parameter Changes
A-
A
Encoder
13
14
15
16
17
18
19
20
21
22
23
24
B-
B
Z-
Z
-
+
Power +V
Common -V
Shield
A-
A
Encoder
13
14
15
16
17
18
19
20
21
22
23
24
B-
B
Z-
Z
-
+