Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

205

Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Appendix E

Table 24 - Terminal Descriptions

A wire must be installed in the hardware thermistor input (X7-28 and X7-
29) and the thermistor short circuit supervisor jumper X10 must be
installed in the OFF position.

OR

A thermistor must be installed in the hardware thermistor input (X7-28
and X7-29).

Term. Blk.

No. Signal

Description

X5

1

SD1+

Isolated Disable input 1 +24V +/-20% 10... 15 mA

2

SD1–

Virtual GND 1

3

SD2+

Isolated Disable input 2 +24V +/-20% 10... 15 mA

4

SD2–

Virtual GND 2

X2

21

Digital Out 1 - N.C.

Max. Resistive Load:
240V AC / 30V DC - 1200VA, 150 W
Max. Current: 5 A, Min. Load: 10 mA
Max. Inductive Load:
240V AC / 30V DC - 8400VA, 105 W
Max. Current: 3.5 A, Min. Load: 10 mA

22

Digital Out 1 Common

23

Digital Out 1 - N.O.

X3

25

Digital Out 2 Common

26

Digital Out 2 N.O.

X7

28

TI1+

Thermistor input: R

trip

4.0 k

Ω

(PTC)

29

TI1–

21 22 23

25 26

1 2 3 4

28 29

ON OFF

X10

X5

X2

X3

X7

IMPORTANT

The drive will not run unless one of the following conditions is met: