DC Input Precharge Control Wiring

If you are installing a DC input drive with a precharge interlock you must make
the following connections on the X50 terminal block from the precharge circuit.
See

Figure 1

on page

27

for additional wiring information.

Table 3 - Frame 9 - X50 Terminal Block Connections

Table 4 - Frames 10…14 - X50 Terminal Block Connections

Table 5 - X50 Terminal Block Specifications (All Frame Sizes)

X50 Terminal Block

Terminal

Description

1

Charge Relay Contact

2

Charge Relay Contact

5

Precharge Complete Signal (+24V DC)

6

Precharge Complete Signal (Common)

X50 Terminal Block

Frame

Terminal

Precharge Circuit Connection Description

10, 11 & 13

21

Charge Relay Contact

23

Charge Relay Contact

25

Precharge Complete Signal (+24V DC)

26

Precharge Complete Signal (Common)

12 & 14

Power Structure 1

21

Charge Relay Contact

23

Charge Relay Contact (Jumper to Power Structure 2
Terminal 21)

25

Precharge Complete Signal (+24V DC)

26

Precharge Complete Signal (Common)

Power Structure 2

21

Charge Relay Contact (Jumper to Power Structure 1
Terminal 23)

23

Charge Relay Contact

25

Precharge Complete Signal (+24V DC)

26

Precharge Complete Signal (Common)

Wire Size Range

(1)

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum

Recommended

6.0 mm

2

(10 AWG)

1.0 mm

2

(18 AWG)

0.8 N

m (7.0 lb

in)