Operating temperatures – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 72
Advertising

72
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 6
Frame 10 Mechanical Installation
Figure 21 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal
Coat)
Operating Temperatures
Frame 10 drives require a minimum of 2600 m
3
/h (1530 cfm) of cooling air.
200 mm
(7.87 in.) Min.
Powerful Performance, Flexible Control.
838 mm
(33.0 in.) Min.
PowerFlex Drive
Voltage Class
Amp Rating
Surrounding Air Temperature
Normal Duty
Heavy Duty
700H & 700S
400/480V AC
(540/650V DC)
All
0…40
°
C
(32…104
°
F)
0…40
°
C
(32…104
°
F)
600/690V AC
(810/932V DC)
261, 325, 385
0…40
°
C
(32…104
°
F)
0…40
°
C
(32…104
°
F)
600/690V AC
(810/932V DC)
416
0…35
°
C
(32…95
°
F)
0…40
°
C
(32…104
°
F)
Advertising