Minimum mounting clearances, Operating temperatures, Minimum mounting clearances operating temperatures – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 134

Advertising
background image

134

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 10

Frame 14 Mechanical Installation

Minimum Mounting
Clearances

Operating Temperatures

Frame 14 drives require a minimum of 4200 m

3

/h (2472 cfm) of cooling air for

each Inverter unit and 1150 m

3

/h (677 cfm) of cooling air for each Converter

unit.

Table 30 - Frame 14 Number of Inverter and Converter Units Per Drive

800 mm

(31.50 in.) Min.

200 mm

(8.0 in.) Min.

1500A Drive - 2400 mm Enclosure Shown.

PowerFlex
Drive

Voltage Class

Amp Rating

Surrounding Air Temperature
Normal Duty

Heavy Duty

700H

400/480V AC
(540/650V DC)

All

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

600/690V AC
(810/932V DC)

1500, 1900

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

600/690V AC
(810/932V DC)

2250

0…35

°

C (32…95

°

F)

0…35

°

C (32…95

°

F)

700S

600/690V AC
(810/932V DC)

1500

0…40

°

C (32…104

°

F)

0…40

°

C (32…104

°

F)

Voltage Class

Amp Rating

No. Converter Units

No. Inverter Units

400/480V AC

1700, 2150

4

6

2700

6

6

600/690V AC

1500

3

6

1900, 2250

4

6