Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 164

Advertising
background image

164

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Appendix A

Specifications

Category

Specification

PowerFlex 700H

PowerFlex 700S

Protection

Drive

380/400V

480V

500V

600V

690V

380/400V

480V

500V

600V

690V

AC Input Overvoltage Trip:

611V AC

611V AC

611V AC

806V AC

806V AC

675V AC

675V AC

675V AC

889V AC

889V AC

AC Input Undervoltage Trip:

235VAC

235VAC

235VAC

326VAC

326VAC

Adjustable

Bus Overvoltage Trip:

911VDC

911VDC

911VDC

1200V DC

1200V DC

911VDC

911VDC

911VDC

1200V DC

1200V DC

Bus Undervoltage Shutoff/Fault:

333VDC

333VDC

333VDC

461VDC

461VDC

Adjustable

Nominal Bus Voltage (Full Load):

517VDC

621VDC

645VDC

776VDC

890VDC

540VDC

648VDC

645VDC

810VDC

931V DC

Heat Sink Thermistor:

Monitored by microprocessor overtemp trip

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
Instantaneous Current Limit:


360% of rated Heavy Duty current (typical)

Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)

Line transients:

up to 6000 volts peak per IEEE C62.41-1991

Up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise Immunity:

Showering arc transients up to 1500V peak

Showering arc transients up to 1500V peak

Power Ride-Thru:

15 milliseconds at full load

15 milliseconds at full load

Logic Control Ride-Thru:

0.5 seconds minimum, 2 seconds typical

0.25 seconds, drive not running

Ground Fault Trip:

Phase-to-ground on drive output

Phase-to-ground on drive output

Short Circuit Trip:

Phase-to-phase on drive output

Phase-to-phase on drive output

Environment

Altitude:

1000 m (3300 ft.) maximum without derating. Derate the drive by 1% for every
100 m (328 ft.) above 1000 m (3300 ft.).

1000 m (3300 ft.) maximum without derating. Derate the drive by 1% for every
100 m (328 ft.) above 1000 m (3300 ft.).

Maximum Surrounding Air Temperature without
De-rating:

Based on drive rating, refer to Drive Ratings on page

167

.

Based on drive rating, refer to Drive Ratings on page

167

.

Storage Temperature (all const.):

–40 to 60° C (–40 to 140° F)

–40 to 70° C (–40 to 158° F)

Atmosphere:

Important: Drive must not be installed in an area where the ambient
atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not
going to be installed for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.

Important: Drive must not be installed in an area where the ambient
atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not
going to be installed for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.

Relative Humidity:

5 to 95% non-condensing

5 to 95% non-condensing

Shock:
Non-operational

15G peak for 11ms duration (

±

1.0 ms)

15G peak for 11ms duration (

±

1.0 ms)

Vibration:

2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6

2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6

Sound:

Frame

Sound Level

Back- ground
Noise Level

Note: Sound pressure level is
measured at 1 meter. All
devices measured are 400V
IP21 and in power up mode.

Frame

Sound Level

Back- ground
Noise Level

Note: Sound pressure level is
measured at 1 meter. All
devices measured are 400V
IP21 and in power up mode.

9

78 dba

49 dba

9

78 dba

49 dba

10

77 dba

49 dba

10

77 dba

49 dba

13

76d ba

46 dba

13

76d ba

46 dba

Electrical

AC Input Voltage Tolerance:

±

10%

±

10%

Frequency Tolerance:

47…63 Hz.

47…63 Hz.

Input Phases:

Three-phase input provides full rating for all drives. Single-phase operation
provides 50% of rated current.

Three-phase input provides full rating for all drives. Single-phase operation
provides 50% of rated current.

Displacement Power Factor:

0.98 across entire speed range.

0.98 across entire speed range.

Efficiency:

97.5% at rated amps, nominal line volts.

97.5% at rated amps, nominal line volts.

Maximum Short Circuit Rating:

200,000 Amps symmetrical.

200,000 Amps symmetrical.

Actual Short Circuit Rating:

Determined by AIC rating of installed fuse/circuit breaker.

Determined by AIC rating of installed fuse/circuit breaker.

Maximum Drive to Motor Power Ratio:

Recommended not greater than 2:1 ratio.

Drive to motor rating cannot exceed a 2:1 ratio.