Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 38

Advertising
background image

38

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 2

Control Wiring for PowerFlex 700H Drives

Analog Input Bipolar Speed
Reference
±10V Input
Important: See the Attention
statement on page

31

for

important information on
bipolar wiring.

Set I/O configuration (see Analog I/O

Configuration on page

36

).

Set parameter 190 [Direction Mode] = 1

“Bipolar”

Adjust Scaling:

Parameters 91 [Speed Ref A Hi] / 92
[Speed Ref A Lo] and 325 [Analog In 2 Hi] /
326 [Analog In 2 Lo]

View Results:

Parameter 002 [Commanded Speed]

Analog Voltage Input
Unipolar Speed Reference
0 to +10V Input

Set I/O configuration (see Analog I/O

Configuration on page

36

).

Configure Input with parameter 320 [Anlg

In Config]

Adjust Scaling:

Parameters 91 [Speed Ref A Hi] / 92
[Speed Ref A Lo] and 325 [Analog In 2 Hi] /
326 [Analog In 2 Lo]

View Results:

Parameter 002 [Commanded Speed]

Analog Current Input
Unipolar Speed Reference
4…20 mA Input

Set I/O configuration (see Analog I/O

Configuration on page

36

).

Configure Input for Current:

Parameter 320 [Anlg In Config] and add
jumper at appropriate terminals

Adjust Scaling:

Parameters 91 [Speed Ref A Hi] / 92
[Speed Ref A Lo] and 325 [Analog In 2 Hi] /
326 [Analog In 2 Lo]

View Results:

Parameter 002 [Commanded Speed]

Analog Input, PTC
0-10V Input
PTC OT set > 5V
PTC OT cleared < 5V
PTC Short < 0.2V

Set I/O configuration (see Analog I/O

Configuration on page

36

).

Configure Analog Input for PTC function:

Set parameter 259 [Alarm Config 1] bit 14
“PTC Config” = Enabled

Configure Analog Input for Fault when

input goes below 0.2V:
Set parameter 324 [Analog In 1 Loss] = 1
“Fault”

Enable Fault:

Set parameter 238 [Fault Config 1] bit 7
“Motor Therm” = Enabled

Enable Alarm:

Set parameter 259 [Alarm Config 1], bit 11
“Motor Therm” = Enabled

Analog Output

±

10V, 4…20 mA Bipolar

+10V Unipolar
(shown)

Set I/O configuration (see Analog I/O

Configuration on page

36

).

Configure with Parameter 340 [Anlg Out

Config]

Select Source Value:

Parameter 384 [Digital Out1 Sel]

Adjust Scaling:

Parameters 343 [Analog Out1 Hi] / 344
[Analog Out1 Lo]

Input/Output

Connection Example

Required Parameter Changes

3
4

3
4

3
4

6

3.32k

Ohm

1.8k

PTC

Ferrite

Bead

1

7

2

8
9

+