Installation on a grounded b phase delta system – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 126

Advertising
background image

126

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 9

Frame 13 Mechanical Installation

If you are installing a 600/690V AC input drive on an ungrounded distribution
system or high resistive ground, you:

Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page

126

.

Must insulate terminal X4 on the rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board o
n page

127

.

Installation on a Grounded B Phase Delta System

If you are installing a drive on a grounded B phase Delta system, you:

Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page

126

.

Must insulate terminal X4 on the rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board o
n page

127

.

Move the Common Mode Jumper(s) to the Disconnected Position

Follow the steps below to move the common mode jumper(s) to the
disconnected position for each converter unit (see

Figure 50

on page

123

for

jumper location).

Task

Description
Loosen the screws and two fasteners that secure the jumper.

Rotate the jumper to the lower position.

Tighten the screw and two fasteners.

A

B

C

A

B

Rectifying Circuit Board

C

Front View of Converter
Unit