Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

159

Frame 14 Mechanical Installation

Chapter 10

Circuit Breaker DIP Switch Settings

The DIP switches on the circuit breakers are configured to the correct settings at
the factory. However, the settings detailed in

Table 32

below should be verified

before charging the circuit breaker motor operators and operating the drive.

Once the settings have been verified, continue with Charging the MCCB Motor
Operators on
page

160

.

Table 32 - Circuit Breaker DIP Switch Settings

Figure 66 - Circuit Breaker DIP Switches Location

Voltage Class

Drive ND
Continuous Amp
Rating

L

S/I

N

I1

t1

S/I

I3

t2

ON/OFF

50% / 100%

400/480V AC

1770

0.76

3 s

S

1.5

0.1 s

OFF

na

2150

0.92

3 s

S

1.5

0.1 s

OFF

na

600/690V AC

1500

0.88

3 s

S

1.0

0.1 s

OFF

na

1900

0.84

3 s

S

1.0

0.1 s

OFF

na

2250

0.96

3 s

S

1.5

0.1 s

OFF

na

OFF

DI

S

CHARGED

S

PRING

L

S

I

N

L

N

I1 =
In x (0.4+

t1

S

I

t2

I2=
In x
I

3

=