Chapter 1

General Installation Information

Figure 3 - Frames 12 and 14 Sample Precharge Wiring Diagram

Table 6 - ASIC Board Charge Relay Contact Ratings

M

F2

R2 CR2

DC+

DC Source

DC-

CR2

R1

F1

M

ASIC

Board

#1

X9

X15

25

26

21

22

23

CR1

M

CR1

CR2

M

M

PU1

X50

Precharge

Complete*

21

23

25

26

Charge

Relay

ASIC

Board

#2

X9

X15

25

26

21

22

23

M

PU2

X50

Precharge

Complete*

21

23

25

26

Charge

Relay

Important: For DC Input Only.
Do Not Install on DC Input Drives.

* Refer to

Table 6

below for contact ratings.

Customer Connections - External Precharge Circuitry
is Shown as Dashed Lines

Terminal Blocks on
Control Frame

Drive
Connections

Load

Resistance load (cos

φ

= 1)

Rated load

8 A at 250 VAC: 5 A at 30 VDC

Rated carry current

8 A

Max. switching voltage

250 VAC; 30 VDC, (400 VAC)

Max. switching current

AC 8 A; DC 5 A

Max. switching power

2,000 VA; 150 W

Failure rate (reference value)

5 VDC 10 mA (for gold plating 0.35 μ min.)