Control Wiring for PowerFlex 700S Drives with Phase II Control

Chapter 3

Hardware Enable Circuitry

By default, Digital Input 6 (Par 830 [Dig In6 Sel]) is configured for hardware
enable input. This is for applications requiring the drive to be disabled without
software interpretation. With the “HW Enable Jumper (Shunt - P22)” on the
pins closest to the PCB (2 and 4), Digital Input 6 is configured as a “dedicated”
hardware enable. See

Figure 1

on page

47

for jumper location. If this

configuration is not required, the “HW Enable Jumper (Shunt)” may be moved
to the out board pins (1 and 3), making Digital Input 6 user programmable via
Par 830 [Dig In6 Sel].

Digital Inputs
Sourcing Digital Inputs -
Internal Power Supply, 2-Wire
Control, 24V DC

Set the value of Par 829 [Dig In5 Sel] to a value of 7 - “Run”
Set bit 8 “3WireControl” of Par 153 [Control Options] to Off (0) for 2-

wire control.

Set Par 168 [Normal Stop Mode] for the desired stopping mode:

0 = Ramp Stop
1 = CurLim Stop
2 = Coast Stop

Digital Inputs
Sourcing Digital Inputs-
Internal Power Supply, 3-Wire,
24V DC

Set the value of Par 829 [Dig In5 Sel] to a value of 14 - “Normal

Stop”

Set Par 828 [Dig In4 Sel] to a value of 5 - “Start”
Set Par 168 [Normal Stop Mode] for the desired stopping mode:

0 = Ramp Stop
1 = CurLim Stop
2 = Coast Stop

Input/Output

Connection Example

Required Parameter Changes

24V DC

Com

Run

Enable

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

24V DC

Com

Start

Enable

Stop

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

Advertising
This manual is related to the following products: