General Installation Information

AC Supply Source
Considerations

Frame 9…14 PowerFlex 700H and 700S drives are suitable for use on a circuit
capable of delivering up to a maximum of 200,000 rms symmetrical amperes, and
a maximum of 690 volts.

If a system ground fault monitor (RCD) is to be used, only Type B (adjustable)
devices should be used to avoid nuisance tripping.

Unbalanced, Ungrounded or Resistive Grounded Distribution
Systems

If phase to ground voltage will exceed 125% of normal or the supply system is
ungrounded, see Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives

, publication

DRIVES-IN001

, for more information.

ATTENTION: To guard against personal injury and/or equipment damage
caused by improper fusing or circuit breaker selection, use only the
recommended line fuses/circuit breakers specified in the drive Technical Data
publications. See Additional Resources on page

17

for a list of technical

publications for PowerFlex 700H and PowerFlex 700S drives.

ATTENTION: PowerFlex 700H and 700S drives contain protective MOVs and
common mode capacitors that are referenced to ground. These devices must be
disconnected if the drive is installed on a resistive grounded distribution system
or an ungrounded distribution system.

If you are
installing a...

see:

Frame 9 drive

Ungrounded, Unbalanced or High Resistive Ground Installations on page

63

Frame 10 drive

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page

79

Frame 11 drive

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page

93

Frame 12 drive

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page

109

Frame 13 drive

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page

123

Frame 14 drive

Ungrounded, High Resistive Ground or Grounded B Phase Delta Installations on page

141