Power wiring – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 84

Advertising
background image

84

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 6

Frame 10 Mechanical Installation

Power Wiring

Table 24 - Power Terminal Specifications

Figure 26 - Power Terminal Locations

IMPORTANT

Once power wiring has been completed, the protective covers must be re-
installed before energizing the drive. Installation is in reverse order of removal
(see Remove the Protective Covers on page

78

).

No.

Name

Description

Wire Size Range

(1)(2)

Torque

Terminal Bolt Size

(3)(4)

Maximum

Minimum

Recommended

1

Input Power Terminal Block

(3)

L1, L2, L3

Input power

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

2

Output Power Terminal Block

(3)

U/T1, V/T2, W/T3

Motor connections

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

3

SHLD Terminal, PE, Motor Ground

(3)

Terminating point for wiring shields

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M10

4

DC Bus

(3)

(2 Terminals; DC–, DC+)

DC input or external brake

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

5

Cable Clamp for Shield

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2) Do Not exceed maximum wire size. Parallel connections may be required.

(3) These connections are bus bar type terminations and require the use of lug type connectors.

(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER